Loading...
Model 5100-28-IT Combustible Gas Sensor Module
Page: 40
Command Specific Response Data Bytes:
Byte Format Description
0 Unsigned-8 Returns new Alarm Level.
Command 132: Set Warning Level
Request Data Bytes:
Byte Format Description
0 Unsigned-8 Warning level, range 0 to 60. Default is 20.
Command Specific Response Data Bytes:
Byte Format Description
0 Unsigned-8 Returns new Warning Level.
Command 133: Set Alarm Relay Action
Request Data Bytes:
Byte Format Description
0 Unsigned-8 0=Latching (default)
2=Non-Latching
Command Specific Response Data Bytes:
Byte Format Description
0 Unsigned-8 Returns new Alarm Relay Action value
Command 134: Set Warning Relay Action
Request Data Bytes:
Byte Format Description
0 Unsigned-8 0=Latching
2=Non-Latching (default)
Command Specific Response Data Bytes:
Byte Format Description
0 Unsigned-8 Returns new Warning Relay Action value
Command 135: Reset Alarms
This command will reset any alarm relays that have been latched, providing the alarm condition is no longer
present on the sensor.
Request Data Bytes: None
Command Specific Response Data Bytes: None