ALrE Alarm Reset: Select OnOF or Hold.
OnOF Automatic Reset.
Hold Manual Reset. Reset (acknowledge) by simultaneously pressing the
INDEX & DOWN ARROW keys for 5 seconds.
ALPi Alarm Power Interrupt: Select On or OFF.
On Alarm Power Interrupt is On.
OFF Alarm Power Interrupt is OFF.
ALiH Alarm Inhibit: Select On or OFF.
On Alarm Inhibit is On. Alarm action is suspended until the process
value first enters a non-alarm condition.
OFF Alarm Inhibit is OFF.
ALSt Alarm Output State: Select CLOS or OPEn.
CLOS Closes Contacts at Alarm Set Point.
OPEn Opens Contacts at Alarm Set Point.
ALLP Alarm Lamp: Select O on or OoFF.
O on Alarm Lamp is ON when alarm contact is closed.
OoFF Alarm Lamp is OFF when alarm contact is closed.
ALLb Alarm Loop Break. Select On or OFF.
On Loop Break Condition will cause an Alarm Condition.
OFF Loop Break will not affect the Alarm Condition.
Addr (Option C4, Serial Communications) Control Address: Set from 1 to 3FF.
This number (hexadecimal, base 16) must match the address number used
by the host computer.
bAUd (Option C4, Serial Communications) Communication Baud Rate: Select
300, 1200, 2400, 4800, 9600, or 19200. This number must match the
baud rate used by the host computer.
nAt (Option C4, Serial Communications) No Activity Timer: Set from OFF or 1
to 99 minutes.
1 - 99 Maximum time between host computer accesses. If timer counts
to 0, CHEC/LorE will be displayed.
OFF No Activity Timer function is disabled.
Stor (Option C4, Serial Communications) Store to EEPROM: Select YES or no.
(See additional information on page 21).
YES Menu Items changes made through the Serial Communications are
stored directly to the EEPROM.
no Menu items changes made through the Serial Communications are
stored directly in RAM.