Loading...
Page 34
DIAGNOSTIC ERROR MESSAGES
DISPLAY MEANING SP OUTPUTS ACTION REQUIRED
No
display
lighted
Display is blank. Inst-
rument is not getting
power, or the supply
voltage is too low.
Set point outputs
inactive
Alarm inactive.
Check that the power
supply is on, or that the
external fuses are good.
Fail test appears
upon power up if the
internal diagnostics
detect a failure. This
message may occur
during operation if a
failure is detected.
Displays flash.
The display alternate
between FAIL tESt and
one of the following mes-
sages: FACt dFLt:
Memory may be corrupt-
ed. Press the ENTER key
and the DOWN ARROW
key to start default factory
procedure. Recheck con-
troller programming. rEt
FACt: Unrecoverable
error, return to factory for
service.
Set point outputs
inactive
Alarm inactive.
FAIL
tESt
CHEC
SP1,
CHEC
SP2,
CHEC
1SP, ...,
CHEC
16SP
This message will
appear upon power
up if SP1, SP2,
#SP1, or ##SP is set
outside of the SPL or
SPH values.
Set point outputs
inactive
Alarm active.
Correct the SP1, etc. or
adjust the SPL or SPH
values by programming
new values
CHEC
SPL or
CHEC
SPH
This message ap-
pears at power up if
SPL or SPH values
are programmed out-
side the input range
ends.
Set point outputs
inactive
Alarm inactive.
Correct the SPL or SPH
values by programming
new values.
CHEC
rSpt
This message ap-
pears if the analog
remote set point sig-
nal is out of range.
Set point outputs
active
Alarm inactive.
The control will revert to
SP1. Correction of the
analog signal allows the
control to return to the
remote.
This message ap-
pears if the Serial
Communications has
timed out.
Set point outputs
active
Alarm active.
Restore the communica-
tions line and switch the
LorE to LOC.
CHEC
LorE
This message ap-
pears if the ambient
temperature of the
control is out of range
or RJC sensor is broken
Set point outputs
active
Alarm active.
Correct the ambient tempera-
ture conditions. Ventilate the
area of the cabinet or check
for clogged filters. If RJC bro-
ken, return to factor for service.
ArEA
(Alternat
es with
PV when
near)
Loading...
Terms of Use | Privacy Policy | DMCA Policy