OBSERVED CONDITION CORRECTIVE ACTION
A. Analog Output 1 .Noise on input. Slowly turn
With No Flow SENS pot CCW until false in
dication stops.
NOTE: In fully CCW position
the unit will not operate.
D. Incorrect Analog 1 .Load resistance too small.
Output with Flow 2. Noise pickup present. Adjust
Sensitivity.
3. Calibration of FLSC-28
incorrect. Recalibrate.
E. Large Ripple on 1 .Wrong “Range” switch
Analog Output selected. Recalibrate.
2. Flowmeter being operated
below range. Adjust response
control to minimize ripple.
SECTION 6 SPECIFICATIONS
INPUT. Input protected, RF and band pass filtered, adjustable
trigger level,
Input Impedance - 40 kilohm (nominal)
Trigger Sensitivity - 10 millivolt RMS (minimum) 10 to 1000 Hz
Over Voltage - 120 volts RMS absolute (maximum)
VOLTAGE OUTPUT: Accuracy ±0.05% of full scale ±200
PPM/°C Range 0-5V
Impedance less than 10 ohms.
Response time .5 - 1.5 seconds, for 10 to 90%, adjustable. Output
ripple less than 0.2% of F.S.
Load resistance output can source up to 10 mA into a grounded
load only.
INPUT POWER: 10-40 Vdc @ 10 mA
TEMPERATURE RANGE: 0°-70°C (32° to 158°F)
ELECTRICAL CONNECTIONS: Screw Terminals
MAXIMUM LEAD LENGTH: 100 ft. of 24 gage copper wire
ELECTRICAL HOUSING: Class 1, Group D
Class 11 Group E, F, G
Class III