30
Refer to Figure 2-2, wiring installation drawing for appropriate
terminals for interconnections. The signal leads from the turbine
should be shielded whenever the FLSC-34 is not integrally
mounted. Ground shield on one end only. If desired, use solder
lug provided on ground stud. Connections to the terminal block
should be carefully dressed to avoid having bare wires extend
pass the screw clamp on the terminal block. This is particularly
important for units mounted within the explosion proof
enclosure. Wires should be neatly dressed near bottom of
enclosure to assure wiring will not become fouled when cover is
installed.
Connect two conductor shielded cable from flowmeter. Connect
shield to FLSC-34 only.
Line power connection should be made through a circuit
breaker so that power can be turned off while servicing the
FLSC-34. Power is 117 Vac ±10%, an earth ground connection is
also required.
Pulse output is CMOS/TTL compatible. Wire to appropriate
terminal, see Figure 2-2.
For Analog Output connect wiring to appropriate terminals and
load. A shielded, twisted pair wire is recommended. Ground
shield on one end only. Use same precautions as described for
flowmeter input signal.
Figure 2-1. Outline and Intallation Dimensions