C. Analog Output 1. Improper wiring terminations.
Correct wiring.
2. FLSC-34 improperly calibrated.
Recalibrate.
3. Defective circuitry within the
FLSC-34. Factory repair FLSC-34.
Refer to flowmeter operator’s manual for repair instructions for the turbine
flowmeter.
SECTION 6 SPECIFICATIONS
INPUT: Input protected, RF and band pass filtered, adjustable
trigger level,
Input Impedance 40 ohm (nominal)
Trigger Sensitivity 10 millivolt RMS (minimum) 10 Hz to
1000 Hz Over Voltage - 120 volts RMS absolute (maximum)
ANALOG OUTPUT: Range 4 to 20 mA.
Controls - Non-interacting zero and span adjustments.
Accuracy ±0.1% F. S. 200 PPM/°C
Maximum Impedance - 325 ohms.
F. S. Frequency Range 75 Hz to2500 Hz (DIP SWITCH
SELECTABLE)
PULSE OUTPUT: TTL/CMOS COMPATIBLE
LOGIC 1; 2.4V AT - .800 mA
LOGIC 0; 0.4 V maximum at 100 ma
INPUT POWER: 115 Vac 50/60 Hz
TEMPERATURE RANGE: 0°-70°C (32° to 158°F)
ELECTRICAL CONNECTIONS: Screw Terminals
MAXIMUM LEAD LENGTH: 1000 ft. of 24 gage copper wire
ELECTRICAL HOUSING: Class 1, Group D
Class 11 Group E, F, G
Class III
NOTE