28
HX86 and the HX86A (Sensor with Electronics Module)
Measured Parameters – RH/Temp.
RH Accuracy – +/- 1% RH
Temp. Accuracy – +/- 0.5oC
Output Information – RH, Temp., DP
Electrical Outputs – 4 to 20 mA (X3)
RS232C
Alarm Relays (X2)
Digital Display – LCD, 2-line
HXB86 and the HX86BA (Sensor with Electronics
Module) Measured Parameters – RH/Temp./Barometric
Pressure RH Accuracy – +/- 1% RH
Temp. Accuracy – +/- 0.5oC
Pressure Accuracy – +/- 5 mb
Output Information – RH, Temp., Pressure
Electrical Outputs – 4 to 20 mA (X3)
RS232C
Alarm Relays (X2)
Digital Display – LCD, 2-line
HXP86 and the HX86PA (Sensor with Electronics Module)
Measured Parameters – RH/Temp./ Pressure
RH Accuracy – +/- 1% RH
Temp. Accuracy – +/- 0.5oC
Pressure Accuracy – +/- 0.75 psi
Output Information – RH, Temp., Pressure
Electrical Outputs – 4 to 20 mA (X3)
RS232C
Alarm Relays (X2)
Digital Display – LCD, 2-line
Electrical Outputs
Systems with Probe only –
0 to 10 Vdc (X 3) @ 10 mA max.
RS232C (bi-directional)
Systems with Probe and Electronics Unit—
4 to 20 mA (X3) into 500 max.
Alarm Relay (X2) Form A (SPST, NO) rated at 3A/250 Vac
RS232C (bi-directional)
Serial Output (All Units)
RS232C to DTE device. 19.2 kilobaud, 8 bits data, 1 stop bit, no parity