5 CiA402 Drive Profile
5 - 10 EtherCAT Communication Unit USER’S MANUAL (I574-E1)
All savable parameters are saved in the Inverter EEPROM.
Saving is executed only when a specific value is written to sub-index 1. This prevents parameter val-
ues from being accidentally overwritten.
The specific value means “save”.
A value of 00000001 hex (command valid) is given when reading.
Parameters cannot be saved to the EEPROM during inverter operation.
In the following cases, an ABORT code is returned.
Writing with CompleteAccess.
Writing a value other than 65766173 hex.
Writing to the EEPROM may take up to 1 second. (This is when all objects are changed.)
There is a limit to the number of times you can write to the EEPROM. For the life (number of writes)
of the EEPROM, refer to the user's manual for the MX2-series or RX-V1-series Inverters.
Inverter parameters are reset to their default settings.
A restoration operation is executed only when a specific value is written to sub-index 1. This prevents
parameter values from being accidentally overwritten.
The specific value means “load.”
A value of 00000001 hex (command valid) is given when reading.
In the following cases, an ABORT code is returned.
Writing with CompleteAccess.
Writing a value other than 64616F6C hex.
Writing to the EEPROM may take up to 3 seconds. (This is when all objects are changed.)
There is a limit to the number of times you can write to the EEPROM. For the life (number of writes)
of the EEPROM, refer to the user's manual for the MX2-series or RX-V1-series Inverters.
1010 hex Store parameters
Sub-index 0: Number of entries
Setting range: Unit: Default setting: 01 hex
Size: 1 byte (U8) Access: RO PDO map: Not possible
Sub-index 1: Save all parameters
Setting range: Unit: Default setting: 00000001 hex
Size: 4 bytes (U32) Access: RW PDO map: Not possible
MSB LSB
evas
65 hex 76 hex 61 hex 73 hex
1011 hex Restore default parameters
Sub-index 0: Number of entries
Setting range: Unit: Default setting: 01 hex
Size: 1 byte (U8) Access: RO PDO map: Not possible
Sub-index 1: Restore all default parameters
Setting range: Unit: Default setting: 00000001 hex
Size: 4 bytes (U32) Access: RW PDO map: Not possible
MSB LSB
dao l
64 hex 61 hex 6f hex 6c hex
All
All