A - 19
Appendices
EtherCAT Communication Unit USER’S MANUAL (I574-E1)
A-4 MX2 Series Parameter List
A
3013
hex
3C
hex
1315 hex Free-electronic
Thermal Current 3
b020 RW 0.00 to rated current 0.01 [%] Possible
(TxPDO)
3013
hex
3D
hex
1316 hex Overload Limit 1
Selection
b021 RW 00: Disabled
01: Enabled during
acceleration/constant speed
02: Enabled during constant speed
03: Enabled during
acceleration/constant speed
(accelerated during
regeneration)
Possible
(TxPDO)
3013
hex
3E
hex
1317 hex Overload Limit 1 Level b022 RW 200 to 2000 0.01 [%] Possible
(TxPDO)
3013
hex
3F
hex
1318 hex Overload Limit 1
Parameter
b023 RW 1 to 30000 0.1 [s] Possible
(TxPDO)
3013
hex
40
hex
1319 hex Overload Limit 1
Selection 2
b024 RW 00: Disabled
01: Enabled during
acceleration/constant speed
02: Enabled during constant speed
03: Enabled during
acceleration/constant speed
(accelerated during
regeneration)
Possible
(TxPDO)
3013
hex
41
hex
131A
hex
Overload Limit 1
Level 2
b025 RW 200 to 2000 0.01 [%] Possible
(TxPDO)
3013
hex
42
hex
131B
hex
Overload Limit 1
Parameter 2
b026 RW 1 to 30000 0.1 [s] Possible
(TxPDO)
3013
hex
43
hex
131C
hex
Overcurrent
Suppression Selection
b027 RW 00: Disabled
01: Enabled
Possible
(TxPDO)
3013
hex
44
hex
131D
hex
Frequency Pull-in
Restart Level
b028 RW 200 to 2000 0.01 [%] Possible
(TxPDO)
3013
hex
45
hex
131E
hex
Frequency Pull-in
Restart Parameter
b029 RW 1 to 30000 0.1 [s] Possible
(TxPDO)
3013
hex
46
hex
131F
hex
Starting Frequency at
Frequency Pull-in
Restart Selection
b030 RW 00: Frequency at interruption
01: Max. frequency
02: Set frequency
Possible
(TxPDO)
3013
hex
47
hex
1320 hex Soft Lock Selection b031 RW 00: Data other than b031 cannot be
changed when terminal SFT is
ON.
01: Data other than b031 and the
set frequency cannot be
changed when terminal SFT is
ON.
02: Data other than b031 cannot be
changed.
03: Data other than b031 and the
set frequency cannot be
changed.
10: Data can be changed during
RUN.
Possible
(TxPDO)
3013
hex
49
hex
1322 hex Motor Cable Length
Code Selection
b033 RW 5 to 20 Possible
(TxPDO)
4013
hex
4A
hex
1323 hex RUN Time/Power ON
Time Level
b034 RW 0 to 65535 10 [h] Possible
(TxPDO)
3013
hex
4C
hex
1325 hex Rotation Direction
Limit Selection
b035 RW 00: No direction limit
01: Only Forward is enabled.
(Reverse is limited.)
02: Only Reverse is enabled.
(Forward is limited.)
Possible
(TxPDO)
3013
hex
4D
hex
1326 hex Reduced Voltage
Startup Selection
b036 RW 0 (Reduced voltage startup time:
small) to 255 (Reduced voltage
startup time: large)
Possible
(TxPDO)
3013
hex
4E
hex
1327 hex Display Selection b037 RW 00: Complete display
01: Individual display of functions
02: User setting, this setting
03: Data comparison display
04: Basic display
05: Monitor display only
Possible
(TxPDO)
3013
hex
4F
hex
1328 hex Initial Screen Selection b038 RW 00: Screen on which the Entry was
last pressed
001 to 060: (d001 to d060)
201: F001
Possible
(TxPDO)
3013
hex
50
hex
1329 hex User Parameter
Automatic Setting
Function
b039 RW 00: Disabled
01: Enabled
Possible
(TxPDO)
3013
hex
51
hex
132A
hex
Torque Limit Selection b040 RW 00: Four-quadrant separate setting
01: Terminal switching
02: Analog voltage input
03: Do not set.
Possible
(TxPDO)
Index Sub-
index
Register
No. Function name Parameter
No. R/W Monitor and setting items
Data
resolution
PDO
map