Loading...
A - 21
Appendices
EtherCAT Communication Unit USER’S MANUAL (I574-E1)
A-4 MX2 Series Parameter List
A
3013
hex
82
hex
135B
hex
Free-run Stop
Selection
b088 RW 00: 0 Hz restart
01: Frequency matching restart
02: Frequency pull-in restart
Possible
(TxPDO)
3013
hex
83
hex
135C
hex
Automatic Carrier
Reduction
b089 RW 00: Disabled
01: Enabled, depends on the
current
02: Enabled, depends on the fin
temperature
Possible
(TxPDO)
3013
hex
84
hex
135D
hex
Usage Rate of
Regenerative Braking
b090 RW 0 to 1000 0.1 [%] Possible
(TxPDO)
3013
hex
85
hex
135E
hex
Stop Selection b091 RW 00: Deceleration stop
01: Free-run stop
Possible
(TxPDO)
3013
hex
86
hex
135F
hex
Cooling Fan Operation b092 RW 00: Always
01: Only during operation
(Including 5 minutes after the
power is turned on and also
after the inverter stops)
02: Depends on the fin temperature
Possible
(TxPDO)
3013
hex
87
hex
1360 hex Cooling Fan Total
Operating Time Clear
b093 RW 00: Operating time count
01: Clear (Return to 00 after clear)
Possible
(TxPDO)
3013
hex
88
hex
1361 hex Initialization Target
Selection
b094 RW 00: All data
01: Data other than
terminal/communications
02: U*** registration function only
03: Other than U*** registration
function
Possible
(TxPDO)
3013
hex
89
hex
1362 hex Regenerative Braking
Selection
b095 RW 00: Disabled
01: Enabled (Disabled during stop)
02: Enabled (Enabled during stop)
Possible
(TxPDO)
3013
hex
8A
hex
1363 hex Regenerative Braking
ON Level
b096 RW 330 to 380/660 to 760 1 [V] Possible
(TxPDO)
3013
hex
8E
hex
1367 hex Free V/f Frequency 1 b100 RW 0 to Free V/f Frequency 2 1 [Hz] Possible
(TxPDO)
3013
hex
8F
hex
1368 hex Free V/f Voltage 1 b101 RW 0 to 8000 0.1 [V] Possible
(TxPDO)
3013
hex
90
hex
1369 hex Free V/f Frequency 2 b102 RW 0 to Free V/f Frequency 3 1 [Hz] Possible
(TxPDO)
3013
hex
91
hex
136A
hex
Free V/f Voltage 2 b103 RW 0 to 8000 0.1 [V] Possible
(TxPDO)
3013
hex
92
hex
136B
hex
Free V/f Frequency 3 b104 RW 0 to Free V/f Frequency 4 1 [Hz] Possible
(TxPDO)
3013
hex
93
hex
136C
hex
Free V/f Voltage 3 b105 RW 0 to 8000 0.1 [V] Possible
(TxPDO)
3013
hex
94
hex
136D
hex
Free V/f Frequency 4 b106 RW 0 to Free V/f Frequency 5 1 [Hz] Possible
(TxPDO)
3013
hex
95
hex
136E
hex
Free V/f Voltage 4 b107 RW 0 to 8000 0.1 [V] Possible
(TxPDO)
3013
hex
96
hex
136F
hex
Free V/f Frequency 5 b108 RW 0 to Free V/f Frequency 6 1 [Hz] Possible
(TxPDO)
3013
hex
97
hex
1370 hex Free V/f Voltage 5 b109 RW 0 to 8000 0.1 [V] Possible
(TxPDO)
3013
hex
98
hex
1371 hex Free V/f Frequency 6 b110 RW 0 to Free V/f Frequency 7 1 [Hz] Possible
(TxPDO)
3013
hex
99
hex
1372 hex Free V/f Voltage 6 b111 RW 0 to 8000 0.1 [V] Possible
(TxPDO)
3013
hex
9A
hex
1373 hex Free V/f Frequency 7 b112 RW 0 to 400 (1000) (Hz) 1 [Hz] Possible
(TxPDO)
3013
hex
9B
hex
1374 hex Free V/f Voltage 7 b113 RW 0 to 8000 0.1 [V] Possible
(TxPDO)
3013
hex
A2
hex
137B
hex
Brake Control
Function Selection
b120 RW 00: Disabled
01: Enabled
Possible
(TxPDO)
3013
hex
A3
hex
137C
hex
Brake Release Wait
Time
b121 RW 0 to 500 0.01 [s] Possible
(TxPDO)
3013
hex
A4
hex
137D
hex
Acceleration Wait
Time
b122 RW 0 to 500 0.01 [s] Possible
(TxPDO)
3013
hex
A5
hex
137E
hex
Stop Wait Time b123 RW 0 to 500 0.01 [s] Possible
(TxPDO)
3013
hex
A6
hex
137F
hex
Brake Wait Time for
Confirmation
b124 RW 0 to 500 0.01 [s] Possible
(TxPDO)
3013
hex
A7
hex
1380 hex Brake Release
Frequency
b125 RW 0 to 40000 0.01 [Hz] Possible
(TxPDO)
3013
hex
A8
hex
1381 hex Brake Release Current b126 RW 0 to 20000 0.01 [%] Possible
(TxPDO)
3013
hex
A9
hex
1382 hex Break ON Frequency b127 RW 0 to 40000 0.01 [Hz] Possible
(TxPDO)
Index Sub-
index
Register
No. Function name Parameter
No. R/W Monitor and setting items
Data
resolution
PDO
map
Loading...
Terms of Use | Privacy Policy | DMCA Policy