2 - 19
2 Starting a Sample System
EtherCAT Communication Unit USER’S MANUAL (I574-E1)
2-5 Mounting and Wiring for the EtherCAT
Communication Unit
2
2-5-2 Mounting the EtherCAT Communication Unit on the RX-V1 Inverter
6Mount the EtherCAT Communication Unit onto the
inverter.
1) Put the two lock pins of the EtherCAT
Communication Unit in the inverter and
push up.
1) Insert the bottom part of the EtherCAT
Communication Unit.
1) Push down the EtherCAT Communication
Unit to fix.
7Connect the grounding cable of the EtherCAT
Communication Unit to the grounding terminal of the
inverter.
Make sure that the grounding terminal is marked with a
grounding symbol.
The position of the grounding terminal varies depending
on the inverter capacity. The figure shows an example.
8Mount the Digital Operator (A) and the terminal cover
and tighten the screws to fix the terminal cover.
Mount the terminal cover below the EtherCAT Commu-
nication Unit to the inverter as before (a).
Tighten the two screws (B).
Note: Keep the removed spacer cover safely.
(c) Push down.
(b) Insert the bottom part.
(a) Push up.
G
a
B
A