2 Starting a Sample System
2 - 24 EtherCAT Communication Unit USER’S MANUAL (I574-E1)
2-6 MX2/RX-V1 Inverter Settings
To perform control from the Communication Unit, the parameter must be changed from the inverter.
In this procedure, the inverter power supply must be turned OFF and then ON again. When the power
supply is turned ON, the inverter may operate in unintended way. Check the condition of the wiring and
system carefully before starting the procedure.
Refer to the User Manual (Cat No.I585 or I578) for the MX2/RX-V1-series inverter for details on operat-
ing the inverter parameter settings and for the meaning of the parameter values.
Set the control method for frequency reference selection and RUN command selection using the
parameters A001 and A002.
Destination Selection Parameter Settings
Destination Selection Parameter Settings
Set the operation of the reset signal.
Note If parameter C102 is not displayed, first set parameter b037 to 01.
Note If parameter C102 is not displayed, first set parameter b037 to 01.
2-6-1 Frequency Reference/RUN Command Setting
Parameter Description Setting
A001 Frequency Reference Selection 1 04: Option
A002 RUN Command Selection 1
Parameter Description Setting
A001 Frequency Reference Selection 05: Option 2
A002 RUN Command Selection
2-6-2 Reset Selection Setting
Parameter
No. Function name Data Default value
C102 Reset Selection 03 (Trip reset only) 00 (Trip reset at power-ON)
Parameter
No. Function name Data Default value
C102 Reset Selection 03 (Trip reset only) 00 (Trip reset at power-ON)