Installation, Operation and Maintenance Manual
󲷇H-A058-E-12󲷈 Diaphragm Valve, True Union Diaphragm Valve (15-50mm, 1/2”-2”) Pneumatic Actuated Type AI
18
(13) Operating procedure
Automatic (Air) Operating Procedure
- When AV valve is equipped with a solenoid valve, do not leave solenoid valve terminal cover off.
(Contact with the terminal will cause an electric shock.)
- Check that the supply pressure of the filter regulator is 0.4MPa{4.1kgf/cm2} or more. (AV valve may
not function.)
- Do not increase the set pressure of the filter regulator is 0.6MPa{6.1kgf/cm2} or more. (AV valve may
malfunction.)
Procedure
1) Supply air to the air supply opening.
2) Check that the air supplying side and the stopper [43]
position are matching.
3) Stop supplying air.
<For the solenoid valve >
Procedure
1) Supply the air to the solenoid valve.
2) Push the button with a finger, and confirm the action mode
shown in the following table.
3) Apply regular rated voltage to the solenoid valve, and
confirm the action mode shown in the following table.
4) Turn off the solenoid valve
Push button
Current
Double
action
Single action
Air to open
Air to close
Pushed
On
Shut
Not pushed
Off
Open
Caution
Warning